1ENVIRONMENTAL SERIESELECTRICALLY HEATED AIR CURTAINS8 KW THROUGH 48 KW36” THROUGH 144”Read Carefully - These instructions are written to help youprev
10* SEE CHARTPLUG/SOCKETCONNECTOR (NO. OF UNITS) X KW LOAD PER UNIT: 1208(3) X 11.25 (3) X 11.25 (3) X 9 (3) X 9 (3) X 6 (3) X 6 240(3) X 15 (3) X 15(
11Figure 10Replacement Parts List for Air Curtain CabinetsRef.No. Description1 Cabinet Intake Grille2 Electric Box Cover3 Front Control Panel4 Motor A
12HOW TO OBTAIN WARRANTY SERVICE ANDWARRANTY PARTS PLUS GENERAL INFORMATION1. Warranty Service or Parts 1-800-642-43282. Purchase Replacement Parts 1-
2Environmental Series Specifications and PerformanceNUMBER AIR DELIVERY @ NOZZLE OUTLET APPROX.MODEL NOZZLE Volts Heater # MOTORS @ OF CONTROL MAX VEL
3GENERAL INFORMATIONAir curtains produce a wall of continuously flowing air that acts asa thermal barrier against outside air and provides protectiona
4Important Note: The portion of the sensing tube that attaches tothe blower has an opening that must face the blower and be posi-tioned near the cente
57. Replace intake grille with louvers facing down and fastenknurled nuts.Field Power Wiring: Refer to Wiring Diagram andNameplate.1. Before wiring be
6For 3 Cabinet Units: 108”, 120”, 132” and 144” See Figure 6NOTE: All installation should be done to meet local building codes.1. Determine mounting l
7TROUBLE SHOOTING CHARTSymptom Possible Cause Corrective ActionFan inoperative 1. Blown fuse or open circuit breaker. 1. Replace fuse or reset circuit
8*SEECHARTPLUG/SOCKETCONNECTORKW LOAD PER UNIT:48016 1612 128820811.25 11.25996624015 1512 1288VOLTS1/2 HP 3/4 HP5075MOTOR CODERL1L2L3G321PLPLPLR1 R1
9*SEECHARTPLUG/SOCKETCONNECTOR(NO. OF UNITS) X KW LOAD PER UNIT:480 (3) X 12 (3) X 12(3) X 8(3) X 8VOLTS 1/2 HP 3/4 HP50 75MOTOR CODERL1 L2 L3G321PLPL